Fujitsu Airstage Eco Circular Cassette Large Rooms 3ph - R32
Single SplitProduct code: Circular Cassette Eco Flow for Large Rooms 3ph

Fujitsu Airstage Eco Circular Cassette Large Rooms 3ph - R32

The Fujitsu ECO Circular Cassette with 3-phase outdoor unit is engineered for powerful, ultra-efficient climate control in large rooms and commercial spaces. Its 360° airflow delivers consistent temperature distribution, making it ideal for open-plan offices, conference areas, retail stores, hospitality venues, and spacious residential environments. Supported by a robust 3-phase power supply, this system offers higher output, improved stability, and reduced electrical load. The slim ceiling cassette blends discreetly into modern interiors, while advanced inverter technology and R32 refrigerant ensure excellent energy efficiency and low running costs. Quiet performance and flexible installation make it a reliable solution for larger projects requiring strong, year-round heating and cooling.

Fujitsu Airstage Eco Circular Cassette Large Rooms 3ph - R32

Model Reference

Cool
Capacity
(kW)
Heat
Capacity
(kW)

Max
Pipe
(m)
EuP Lot 10
Energy Rating

Suggested MCB
(A)

Pipe
Size
Gas

Pipe
Size
Liquid

Electrical
Supply

Wi-Fi
Control
Indoor Unit Outdoor Unit SCOP SEER
AUXG36KRLB AOEG36KQTA 9.5 10.8 30 4.0 6.1 16 5/8 3/8 Three Optional
AUXG45KRLB AOEG45KQTA 12.1 13.5 30 3.8 5.40 16 5/8 3/8 Three Optional
AUXG54KRLB AOEG54KQTA 13.4 13.7 30 3.85 6.00 16 5/8 3/8 Three Optional

For more information, see Technical Specifications.


Key features

Unique Circular Flow Design for Full-Room Comfort

Unique Circular Flow Design for Full-Room Comfort

The Fujitsu Circular Cassette achieves true 360° airflow, ensuring balanced temperature distribution across the entire space. Powered by a high-efficiency DC fan motor and turbo fan, and enhanced by a seamless airflow louver design, the system delivers strong, smooth air movement that eliminates hot and cold spots and creates optimal comfort in any environment.

Individual Louver Control

Individual Louver Control

Each louver can be adjusted independently using the touch-panel wired controller, allowing airflow to be directed precisely according to the room layout.

Compatible with UTY-RNRYZ5 wired remote controller.

Redesigned Compact and Lightweight Outdoor Unit

Redesigned Compact and Lightweight Outdoor Unit

The outdoor units used in the 45,000 BTU and 54,000 BTU models have been fully redesigned to deliver a smaller, lighter, and more installation-friendly format. This improved structure simplifies handling on-site and allows for easier placement in tight or challenging outdoor locations, enhancing both installation efficiency and flexibility.

Central Control System Integration (Optional)

Central Control System Integration (Optional)

For enhanced building management, the system can link with a range of central control platforms. By integrating via optional MODBUS or KNX interfaces, users can centrally monitor and control not only air conditioning but also other facility equipment, providing a unified and efficient control solution.

Fujitsu Airstage Eco Circular Cassette Large Rooms 3ph - R32-Fujitsu Airstage-Oceanair
Fujitsu Airstage Eco Circular Cassette Large Rooms 3ph - R32-Fujitsu Airstage-Oceanair
Fujitsu Airstage Eco+ Range KN Series Wall Mounted - R32-Fujitsu Airstage-Oceanair
Fujitsu Airstage Eco Circular Cassette Large Rooms 3ph - R32-Fujitsu Airstage-Oceanair
Fujitsu Airstage Eco Circular Cassette Large Rooms 3ph - R32-Fujitsu Airstage-Oceanair
Technical Data Model Pairing (Indoor + Outdoor Unit)
AUXG36KRLB + AOEG36KQTA AUXG45KRLB + AOEG45KQTA AUXG54KRLB + AOEG54KQTA
Power Source 3-phase, ~400 V, 50 Hz
Cooling Capacity (Rated) kW 9.512.113.4
Cooling Capacity (Min–Max) kW 2.8–10.64.0–12.64.5–13.8
Heating Capacity (Rated) kW 10.813.513.7
Heating Capacity (Min–Max) kW 2.7–12.54.2-15.04.7–16.0
Input Power Cooling / Heating (kW) 3.06 / 2.58 4.32 / 3.77 4.87 / 4.86
EER (Cooling) W/W 3.102.802.75
COP (Heating) W/W 4.193.583.19
Pdesign (Cooling / Heating -10°C) kW 9.5 / 8.712.1 / 9.213.4 / 9.5
SEER (Cooling) W/W 6.15.46.00
SCOP (Heating) W/W 4.03.83.85
Energy Efficiency Class (Cooling / Heating) A++/A+ - -
Max Operating Current (Cooling / Heating) A 10.5/10.5 13.6/13.6 13.6/13.6
Annual Energy Consumption – Cooling (kWh/a) 545--
Annual Energy Consumption – Heating (kWh/a) 3,044--
Sound Pressure Level Indoor (Cooling) H/M/L/Q dB(A) 44/41/38/34 46/42/39/35 47/43/40/36
Sound Pressure Level Indoor (Heating) H/M/L/Q dB(A) 44/41/38/34 46/42/39/35 47/43/40/36
Sound Pressure Level Outdoor (Cooling/Heating) High dB(A) 55 / 55 60/ 60 61/ 61
Sound Power Level Cooling / Heating (Indoor High) dB(A) 58 / 58--
Sound Power Level Cooling / Heating (Outdoor High) dB(A) 70 / 70--
Airflow Rate Indoor/Outdoor (Cooling) High m³/h 1,870 / 3,750 2,000 / 4,450 2,100 / 4,450
Airflow Rate Indoor/Outdoor (Heating) High m³/h 1,870 / 3,750 2,000 / 4,780 2,100 / 4,780
Dimensions Indoor (H × W × D) mm 288 × 840 × 840 288 × 840 × 840 288 × 840 × 840
Dimensions Outdoor (H × W × D) mm 788 × 940 × 320 998 × 940 × 320 998 × 940 × 320
Weight Indoor / Outdoor (kg) 29 / 63 29 / 62 29 / 63
Pipe Diameter (Liquid / Gas) mm 9.52 / 15.88 9.52 / 15.88 9.52 / 15.88
Max Pipe Length (Pre-charge) m 30 (30)30 (30)30 (30)
Operating Range (Cooling) °CDB -10 to 46
Operating Range (Heating) °CDB -15 to 24
Refrigerant (GWP) R32 (675)
Cassette Grille Model UTG-UKYA-W / UTG-UKYC-W / UTG-UKYA-B
Dimensions (H × W × D) mm 53 × 950 × 950
Weight (kg) 6.0